Skip to content
StratQuad

Threats

Rockwell Automation Studio 5000 Logix Designer authentication key bypass

CVE-2021-22681Known exploitedCritical

Studio 5000 Logix Designer and RSLogix 5000 use a key to verify that Logix controllers are communicating with legitimate Rockwell Automation design software. An attacker with network access to a controller can discover this key and bypass the verification mechanism. This allows an unauthorised application to connect to and communicate with Logix controllers, potentially enabling unauthorised modifications to industrial control systems.

Plain English summary of the NVD and CISA text, checked by machine against both.

Scores and dates

CVSS 3.1
9.8
CRITICAL
EPSS score
0.64
Probability of exploitation in 30 days
EPSS percentile
99th
Share of scored CVEs at or below this one
Added to KEV
5 Mar
CISA due date
26 Mar
Applies to US federal agencies

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Daily EPSS score, 3 Nov to 15 Nov, source FIRST

Detail

Rockwell, multiple products. CISA required action: Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.

Weakness: CWE-522 (opens in a new tab)

Affected versions

  • rockwellautomation factorytalk services platform: from 2.10
  • rockwellautomation rslogix 5000: from 16, up to 20
  • rockwellautomation studio 5000 logix designer: from 21.0